Replication Data for: MultiPACK Project_The MultiPACK project: installation and monitoring of integrated commercial refrigeration systems in South Europe |
Identification Number: |
doi:10.18710/USMPRX |
Distributor: |
DataverseNO |
Date of Distribution: |
2021-10-04 |
Version: |
1 |
Bibliographic Citation: |
Tosato, Giacomo; Minetto, Silvia; Hafner, Armin, 2021, "Replication Data for: MultiPACK Project_The MultiPACK project: installation and monitoring of integrated commercial refrigeration systems in South Europe", https://doi.org/10.18710/USMPRX, DataverseNO, V1 |
Citation |
|
Title: |
Replication Data for: MultiPACK Project_The MultiPACK project: installation and monitoring of integrated commercial refrigeration systems in South Europe |
Identification Number: |
doi:10.18710/USMPRX |
Authoring Entity: |
Tosato, Giacomo (Enex srl) |
Minetto, Silvia (National Research council, Construction Technology Institute) |
|
Hafner, Armin (NTNU – Norwegian University of Science and Technology) |
|
Producer: |
NTNU – Norwegian University of Science and Technology |
Distributor: |
DataverseNO |
Distributor: |
NTNU – Norwegian University of Science and Technology |
Access Authority: |
Söylemez, Engin |
Depositor: |
Söylemez, Engin |
Date of Deposit: |
2021-09-24 |
Holdings Information: |
https://doi.org/10.18710/USMPRX |
Study Scope |
|
Keywords: |
Engineering, Commercial Refrigeration, Carbon Dioxide, Heat Recovery, Domestic hot water, Energy Efficiency, Evaporators, Europe |
Abstract: |
This dataset includes the data for two transcritical CO2 refrigeration systems installed in Italy and Portugal within the project MultiPACK. The real performance of the units providing refrigeration and space air condition is measured. the data was collected from two different sites/units:<br><br>The unit in Central Italy The unit is based on a booster concept with parallel compression and expansion work recovery by means of ejectors for both vapour pre-compression and liquid recirculation. Semi-hermetic compressors are installed, three compressors for each suction pressure level. For each suction group, one out of the three compressors is inverter-driven to allow a smoother capacity modulation. The unit delivers the heating demand and the cooling loads of the supermarket by means of an Air Handling Unit AHU. The CO2 directly flows through the heating and cooling coils of the AHU.<br><br>The unit in Portugal The MultiPACK system is based on a booster concept with parallel compression and expansion work recovery by ejectors for both vapour pre-compression and liquid recirculation.<br><br>Semi-hermetic compressors are installed, three compressors for both MT and LT suction groups and four compressors for the Auxiliary compression suction group. For each suction group, one compressor is inverter-driven to allow a smoother capacity modulation. The unit also delivers the entire heating and cooling loads of the supermarket by means of two air handling units AHU. |
Methodology and Processing |
|
Sources Statement |
|
Data Access |
|
Other Study Description Materials |
|
Related Publications |
|
Citation |
|
Title: |
The MultiPACK project: installation and monitoring of integrated commercial refrigeration systems in South Europe, 18th European Conference The Latest Technology in Refrigeration and Air Conditioning, Milan, 6-7 June 2019 |
Identification Number: |
https://www.ntnu.edu/documents/1272037961/0/The+MultiPACK+project+-+installation+and+monitoring+of+integrated+commercial+refrigeration+systems+in+South+Europe.pdf/de5539bf-f5d5-874f-a197-a97a307105d8?t=1623176904882 |
Bibliographic Citation: |
The MultiPACK project: installation and monitoring of integrated commercial refrigeration systems in South Europe, 18th European Conference The Latest Technology in Refrigeration and Air Conditioning, Milan, 6-7 June 2019 |
Label: |
00_README_file.txt |
Notes: |
text/plain |
Label: |
01_Research-data_Italy.txt |
Notes: |
text/plain |
Label: |
02_Research-data_Portugal.txt |
Notes: |
text/plain |
Label: |
03_Figure_1.png |
Notes: |
image/png |
Label: |
04_Figure-2_Layout.pdf |
Notes: |
application/pdf |
Label: |
05_Table_1.PNG |
Notes: |
image/png |