<codeBook xmlns="ddi:codebook:2_5" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="ddi:codebook:2_5 https://ddialliance.org/Specification/DDI-Codebook/2.5/XMLSchema/codebook.xsd" version="2.5"><docDscr><citation><titlStmt><titl>Experimental investigation on integrated two-stage evaporators for CO2 heat-pump chillers</titl><IDNo agency="DOI">doi:10.18710/BSOG2S</IDNo></titlStmt><distStmt><distrbtr source="archive">DataverseNO</distrbtr><distDate>2022-06-24</distDate></distStmt><verStmt source="archive"><version date="2022-06-24" type="RELEASED">1</version></verStmt><biblCit>Hafner, Armin; Hazarika, Mihir Mouchum; Lechi, Federico; Zorzin, Alvaro; Pardiñas, Ángel Álvarez; Banasiak, Krzysztof, 2022, "Experimental investigation on integrated two-stage evaporators for CO2 heat-pump chillers", https://doi.org/10.18710/BSOG2S, DataverseNO, V1</biblCit></citation></docDscr><stdyDscr><citation><titlStmt><titl>Experimental investigation on integrated two-stage evaporators for CO2 heat-pump chillers</titl><IDNo agency="DOI">doi:10.18710/BSOG2S</IDNo></titlStmt><rspStmt><AuthEnty affiliation="NTNU – Norwegian University of Science and Technology">Hafner, Armin</AuthEnty><AuthEnty affiliation="NTNU – Norwegian University of Science and Technology">Hazarika, Mihir Mouchum</AuthEnty><AuthEnty affiliation="Business Unit Brazed &amp; Fusion Bonded Heat Exchangers, Alfa Laval Spa, Italy">Lechi, Federico</AuthEnty><AuthEnty affiliation="Business Unit Brazed &amp; Fusion Bonded Heat Exchangers, Alfa Laval Spa, Italy">Zorzin, Alvaro</AuthEnty><AuthEnty affiliation="Thermal Energy, SINTEF Energy Research, Trondheim">Pardiñas, Ángel Álvarez</AuthEnty><AuthEnty affiliation="NTNU – Norwegian University of Science and Technology">Banasiak, Krzysztof</AuthEnty></rspStmt><prodStmt><producer abbr="NTNU">NTNU – Norwegian University of Science and Technology</producer></prodStmt><distStmt><distrbtr source="archive">DataverseNO</distrbtr><distrbtr affiliation="NTNU – Norwegian University of Science and Technology" abbr="NTNU" URI="https://dataverse.no/dataverse/ntnu">NTNU – Norwegian University of Science and Technology</distrbtr><contact affiliation="NTNU – Norwegian University of Science and Technology" email="armin.hafner@ntnu.no">Hafner, Armin</contact><contact affiliation="NTNU – Norwegian University of Science and Technology" email="mihir.m.hazarika@ntnu.no">Hazarika, Mihir Mouchum</contact><depositr>Hazarika, Mihir Mouchum</depositr><depDate>2022-05-11</depDate></distStmt><holdings URI="https://doi.org/10.18710/BSOG2S"/></citation><stdyInfo><subject><keyword xml:lang="en">Engineering</keyword><keyword>Gravity-fed evaporator</keyword><keyword>ejector</keyword><keyword>R744</keyword><keyword>heat-pump chiller</keyword></subject><abstract date="2022-05-11">In this experimental study the performance of novel compact evaporator configuration was investigated. What makes this evaporator configuration unique is the integration of a gravity-fed/ self-circulation evaporator loop on one side of a plate heat exchanger (pre-cooling the secondary flow) and an ejector-assisted circulation loop on the other side (after-cooling the secondary flow). The secondary loop is internally connected, which means that larger temperature differences can be obtained with less connection work and space required, compared to previous heat exchanger models.
Current CO2 heat-pump chillers available on the market utilize two evaporators to achieve high energy efficiency values. Space saving of the new compact design is a desired solution from vendors. When using this new concept, only one ‘three-circuit’ brazed heat exchanger is needed. The experimental campaign proofed that an ejector integration enables the two-stage evaporation configuration which significantly elevates the compressor suction pressure and improves the overall system performance. These systems can be applied in several market sectors including industrial chillers with high-capacity demands, where the secondary fluid is cooled even below 0°C.
An image of the prototype heat exchanger with measuring instruments is shown in the attached figure. The experimental tests are carried out to investigate the performance under different conditions of evaporation pressure, secondary fluid temperature, and secondary fluid flowrate. The results are uploaded here in two files.</abstract><sumDscr/></stdyInfo><method><dataColl><sources/></dataColl><anlyInfo/></method><dataAccs><setAvail/><useStmt/><notes type="DVN:TOU" level="dv">&lt;a href="http://creativecommons.org/publicdomain/zero/1.0">CC0 1.0&lt;/a></notes></dataAccs><othrStdyMat/></stdyDscr><otherMat ID="f155599" URI="https://dataverse.no/api/access/datafile/155599" level="datafile"><labl>00_README_file.txt</labl><txt>Readme file showing the descriptions of how the data are presented in the attached files.</txt><notes level="file" type="DATAVERSE:CONTENTTYPE" subject="Content/MIME Type">text/plain</notes></otherMat><otherMat ID="f155598" URI="https://dataverse.no/api/access/datafile/155598" level="datafile"><labl>figure.tif</labl><txt>Image of the prototype two-stage BPHX with all measuring instruments installed in the test-rig</txt><notes level="file" type="DATAVERSE:CONTENTTYPE" subject="Content/MIME Type">image/tiff</notes></otherMat><otherMat ID="f155567" URI="https://dataverse.no/api/access/datafile/155567" level="datafile"><labl>Two-stageEvp Vs WaterFlow.csv</labl><txt>This .csv file presents the data for two-stage evap.  with change in water flowrate</txt><notes level="file" type="DATAVERSE:CONTENTTYPE" subject="Content/MIME Type">text/comma-separated-values</notes></otherMat><otherMat ID="f155568" URI="https://dataverse.no/api/access/datafile/155568" level="datafile"><labl>Two-stageEvp Vs WaterTemp.csv</labl><txt>This .csv file presents the data for two-stage evap.  with change in water temperatrue</txt><notes level="file" type="DATAVERSE:CONTENTTYPE" subject="Content/MIME Type">text/comma-separated-values</notes></otherMat></codeBook>